Load Current : 25 Amp To 50 Amp Type: HPARC - 480 - 25 A
Highlights : • Energy Saving • High current capacity • Simple wiring • Solid State reliability • Low hysteresis effect • Rugged and compact • Epoxy encapsulated • Operates down to 100 mA
Specifications : Input 3 and 4 • 250 K at 480 VAC (fully off) • Full wave control
Output 1 and 2 • Triac full wave AC • Off State Voltage 400 V • Leakage Current 6 mA • Max rating 25 Amps • Peak Single Cycle Surge Current at 50 Hz = 250 Amps • Hysteresis 15% typical
Protection : • Insulation Connectors to heat sink 1500 V RMS Min • Snubber network 0.1 luF 100 R • Hermetically Sealed
Mode of Operation : The PACR provides a variable output voltage to the load, dependent on the resistance value of the control pot, wired across input connections 3 and 4. When the control potentiometer is set a minimum resistance the full output voltage will be see across the load
PACR - 480 - 25 A : The PACR series are high power, full wave AC phase angle controllers in a compact package capable of regulating up to 6 KW (2 Samps) 480 VAC. The PACR series of regulators govern the amount of power supplied to the load by controlling the phase angle of the AC supply. The low thermal impedance and high electrical isolation provide the equipment designer with a greater flexibility in a wide variety of applications.
Note : • Control Potto load is not isolated exercise caution in-handling this product to aviod the risk of electric shock • The PACR AC Power Controllers should be mounts preferably on a clear unpainted metal or thermally conductive surface, using heat sink compound thinly applied between the controller and the mounting surface